GE Hydran M2 Online Dissolved Gas Analyzer
GE Grid Solutions · Hydran M2
Chemical
Modbus RTU
RS-485
✓ Official
Online dissolved gas analyzer for continuous monitoring of H2, CO, CO2, and CH4 in transformer oil. ±15% accuracy, RS-485 Modbus, 4-gas continuous DGA for incipient fault detection. Industry standard for power transformer fleet health monitoring.
Specifications
| Accuracy | ±15% of reading |
| Gases Monitored | H2, CO, CO2, CH4 |
| Operating Temp (°C) | -40.0–70.0 °C |
| Supply Voltage (V) | 18.0–30.0 V |
| Update Rate | Continuous |